WEKO3
アイテム
交流励磁型同期機の不平衡突発短絡に関する解析 (第2報) ー線地絡故障ー
https://kitami-it.repo.nii.ac.jp/records/6570
https://kitami-it.repo.nii.ac.jp/records/657091f90066-497b-4c30-a862-d04db1255e1a
名前 / ファイル | ライセンス | アクション |
---|---|---|
![]() |
|
Item type | 紀要論文 / Departmental Bulletin Paper(1) | |||||
---|---|---|---|---|---|---|
公開日 | 2007-04-09 | |||||
タイトル | ||||||
タイトル | 交流励磁型同期機の不平衡突発短絡に関する解析 (第2報) ー線地絡故障ー | |||||
言語 | ja | |||||
言語 | ||||||
言語 | jpn | |||||
資源タイプ | ||||||
資源 | http://purl.org/coar/resource_type/c_6501 | |||||
タイプ | departmental bulletin paper | |||||
その他のタイトル | ||||||
その他のタイトル | Analysis of the Unsymmetrical Sudden Short-Circuit of an AC Excited Synchronous Machine (Part 2)-One Line-to-Ground Fault- | |||||
言語 | en | |||||
著者 |
田村, 淳二
× 田村, 淳二× 村田, 年昭× 武田, 郁夫× 長谷川, 淳× 藤原, 一 |
|||||
著者別名 | ||||||
識別子Scheme | WEKO | |||||
識別子 | 33120 | |||||
姓名 | Junji, TAMURA | |||||
言語 | en | |||||
著者別名 | ||||||
識別子Scheme | WEKO | |||||
識別子 | 33121 | |||||
姓名 | Toshiaki, MURATA | |||||
言語 | en | |||||
著者別名 | ||||||
識別子Scheme | WEKO | |||||
識別子 | 33122 | |||||
姓名 | Ikuo, TAKEDA | |||||
言語 | en | |||||
著者別名 | ||||||
識別子Scheme | WEKO | |||||
識別子 | 33123 | |||||
姓名 | Jun, HASEGAWA | |||||
言語 | en | |||||
著者別名 | ||||||
識別子Scheme | WEKO | |||||
識別子 | 33124 | |||||
姓名 | Hajime, FUJIWARA | |||||
言語 | en | |||||
抄録 | ||||||
内容記述タイプ | Abstract | |||||
内容記述 | The line-to-line fault of AESM was analyzed in the preceding paper. In this paper, analysis of the one line-to-ground fault is presented. As we intend to use the AESM as a driving motor-generator in the flywheel energy storage system, it is necessary to analyze the above single-phase asymmetrical faults (line-to-line and one line-to-ground). First, after brief discussion of the line-to-line fault, the basic differential equations for the one line-to-ground fault of a secondary winding are derived. Next the solutions for that fault are derived from the solutions for the line-to-line fault of a secondary winding by transformation of circuit constants and variables. Furthermore the fault of a primary winding is also analyzed and the solutions are derived from those for the line-to-line fault by the same transformation. Finally the short-circuit torques for the line-to-line fault and one line-to-ground fault are discussed | |||||
言語 | en | |||||
書誌情報 |
ja : 北見工業大学研究報告 巻 16, 号 2, p. 79-88, 発行日 1985-03 |
|||||