@article{oai:kitami-it.repo.nii.ac.jp:00006570, author = {田村, 淳二 and 村田, 年昭 and 武田, 郁夫 and 長谷川, 淳 and 藤原, 一}, issue = {2}, journal = {北見工業大学研究報告}, month = {Mar}, note = {application/pdf, The line-to-line fault of AESM was analyzed in the preceding paper. In this paper, analysis of the one line-to-ground fault is presented. As we intend to use the AESM as a driving motor-generator in the flywheel energy storage system, it is necessary to analyze the above single-phase asymmetrical faults (line-to-line and one line-to-ground). First, after brief discussion of the line-to-line fault, the basic differential equations for the one line-to-ground fault of a secondary winding are derived. Next the solutions for that fault are derived from the solutions for the line-to-line fault of a secondary winding by transformation of circuit constants and variables. Furthermore the fault of a primary winding is also analyzed and the solutions are derived from those for the line-to-line fault by the same transformation. Finally the short-circuit torques for the line-to-line fault and one line-to-ground fault are discussed}, pages = {79--88}, title = {交流励磁型同期機の不平衡突発短絡に関する解析 (第2報)* -一線地絡故障-}, volume = {16}, year = {1985} }