Integration of space vector pulse width modulation controlled STATCOM with wind farm connected to multimachine power system

https://kitami-it.repo.nii.ac.jp/records/8409
https://kitami-it.repo.nii.ac.jp/records/8409
fb16313d-1bf3-40aa-b07d-83cdf4e87626
名前 / ファイル ライセンス アクション
2009-01+Renewable+and+Sustainable+Energy+(Muyeen)+STATCOM_9Bus.pdf 2009-01+Renewable+and+Sustainable+Energy+(Muyeen)+STATCOM_9Bus.pdf (945.4 kB)
Item type 学術雑誌論文 / Journal Article(1)
公開日 2016-08-19
タイトル
タイトル Integration of space vector pulse width modulation controlled STATCOM with wind farm connected to multimachine power system
言語 en
言語
言語 eng
資源タイプ
資源 http://purl.org/coar/resource_type/c_6501
タイプ journal article
アクセス権
アクセス権 open access
アクセス権URI http://purl.org/coar/access_right/c_abf2
著者 S., M. Muyeen

× S., M. Muyeen

en S., M. Muyeen

Search repository
Hany., M. Hasanien

× Hany., M. Hasanien

en Hany., M. Hasanien

Search repository
Takahashi, Rion

× Takahashi, Rion

en Takahashi, Rion

Search repository
Murata, Toshiaki

× Murata, Toshiaki

en Murata, Toshiaki

Search repository
Tamura, Junji

× Tamura, Junji

en Tamura, Junji

Search repository
抄録
内容記述タイプ Abstract
内容記述 In this work, dynamic and transient characteristics of a multimachine power system connected with two wind farms composed of fixed speed wind turbinegenerator systems (WTGS) are analyzed. At each wind farm the terminal one space vector pulse width modulation controlled voltage source converter based static synchronous compensator (STATCOM) is considered to be connected. The capacitor bank capacity of fixed speed wind generator is reduced by certain percentages when a STATCOM is integrated at a wind farm terminal. As wind speed is always fluctuating, the terminal voltage of a fixed speed wind generator also fluctuates randomly, which has an adverse effect on the rest of the power system. It is reported that the STATCOM with a reduced capacitor bank can decrease the voltage fluctuations of the multimachine power system as well as wind generator terminals. Moreover, it is shown that a STATCOM can also enhance the transient stability of induction and synchronous generators when a network disturbance occurs in the power system. Since shaft system modeling of a wind turbine has a significant effect on the transient stability analysis of WTGS, a two-mass shaft model is adopted in this study. Both of the symmetrical and the unsymmetrical faults are analyzed in light of the real wind farm grid code. The transient performance of a STATCOM on the network is evaluated by the transient stability index based on the total kinetic energy of generators. For dynamic performance evaluation, real wind speed data are used in the simulation. Finally, it is concluded that the STATCOM can enhance both dynamic and transient stability of wind farms connected with a multimachine power system.
書誌情報 Journal of Renewable and Sustainable Energy

巻 1, 号 1, p. 1-15, 発行日 2009-01
DOI
識別子タイプ DOI
関連識別子 https://doi.org/10.1063/1.3049348
権利
権利情報 c 2009 American Institute of Physics.
出版者
出版者 American Institute of Physics (AIP)
著者版フラグ
言語 en
値 publisher
出版タイプ
出版タイプ VoR
出版タイプResource http://purl.org/coar/version/c_970fb48d4fbd8a85
戻る
0
views
See details
Views

Versions

Ver.1 2021-03-01 06:30:26.430604
Show All versions

Share

Mendeley Twitter Facebook Print Addthis

Cite as

エクスポート

OAI-PMH
  • OAI-PMH JPCOAR 2.0
  • OAI-PMH JPCOAR 1.0
  • OAI-PMH DublinCore
  • OAI-PMH DDI
Other Formats
  • JSON
  • BIBTEX

Confirm


Powered by WEKO3


Powered by WEKO3