@article{oai:kitami-it.repo.nii.ac.jp:00008420, author = {矢神, 雅規 and 柴田, 真輔 and 村田, 年昭 and 田村, 淳二}, issue = {2}, journal = {電気学会論文誌B}, month = {Feb}, note = {This paper presents the results of analyses of the effectiveness of a superconducting fault current limiter (SFCL) to stabilize the synchronous generators, suppress turbine shaft torque oscillations, and limit the fault current in a two-machine-infinite bus system. In this study, the system model with two SFCLs having shunt resistance installed at each generator terminal was used taking 3LG (three lines to ground) fault at 12 fault points into account. These analyses were performed using EMTP/ATP. It is concluded that the use of SFCL with shunt resistance value of 1.1 pu is most effective for all fault points for the stabilization of synchronous generators, the suppression of turbine shaft torque oscillations, and the limitation of fault current.}, pages = {133--142}, title = {多機系統における同期発電機の超電導限流器による安定化に関する検討-2機無限大母線系統による解析 -}, volume = {123}, year = {2003} }