@article{oai:kitami-it.repo.nii.ac.jp:00008419, author = {田村, 淳二 and 世永, 茂 and 松村, 喜治 and 水野, 隆裕 and 鈴木, 伸一}, issue = {1}, journal = {電気学会論文誌B}, month = {Jan}, note = {In standard simulations of short circuit faults in power systems, it is common to neglect transients of the transmission networks and armature circuits of generators. Therefore, it is not possible by standard method to evaluate particular phenomenon arised from the armature transient. It is well known that the standard method can not evaluate the backswing phenomenon caused by the armature transient. This paper applies a new method, which can approximate the DC offset currents that arise from the armature transient, to transient stability simulation of power system including wind generators.}, pages = {106--107}, title = {過渡直流電流を考慮した風力発電機の過渡安定度シミュレーション}, volume = {123}, year = {2003} }