@article{oai:kitami-it.repo.nii.ac.jp:00006236, author = {金山, 公夫 and 仲島, 民雄}, issue = {4}, journal = {北見工業大学研究報告}, month = {Dec}, note = {application/pdf, The measurements of room temperature, floor and wall temperature, radiation energy and others, in accordance with each variation of steam pressure and temperature, were taken with respect to the radiant heating system introduced in the new gymnasium of Kitami Institute of Technology. Namely, the comparisons between the measured values and the graphically calculated values of radation energy were made, and the approximate agreement was obtained. Because the system have well enough heating power, if it is to be operated with full power at initial time, it may be reduced below a half of full load at day time, even in the cold season.}, pages = {539--553}, title = {ふく射暖房装置の性能実験}, volume = {2}, year = {1969} }